System-sensor PDRP-1002 Series Manual de usuario Pagina 18

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 60
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 17
2. Installation Initiating Device Circuits
18
PDRP-1002 Instruction Manual PN 51135:B0 04/06/01
Initiating Device Circuits
The control panel provides two Initiating Device Circuits (#1 and #2) and they may be configured as either
Style D (Class A) or Style B (Class B). Circuit #3 is designated as an Abort Switch Circuit and Circuit #4
is a Manual Release Circuit.
Initiating devices include: Heat, Photoelectric and Ionization type detectors, Manual Pull Stations and
Waterflow alarm devices.
Note: Refer to "Appendix B: Compatible Devices" on page 41 for compatible devices.
Wire all alarm initiating devices sequentially for proper supervision.
Observe polarity when connecting polarized devices.
All circuits are supervised and power-limited.
Leave dummy load resistor (provided) on all unused circuits.
Figure 7 Initiating Device Circuits
Style D (Class A)
Initiating Device
Circuit
Style B (Class B)
Initiating Device
Circuit
4.7K, 1/2-Watt resistor
PN 71252 (UL listed)
Style B (Class B)
Abort Switch
Circuit
Two-wire
Smoke
Detector
Manual
Pull Station
Heat
Detector
Style B (Class B)
Manual Release
Circuit
MRP44-idc.cdr
Note: Silk screen printing on circuit board moved to bottom for clarity
Vista de pagina 17
1 2 ... 13 14 15 16 17 18 19 20 21 22 23 ... 59 60

Comentarios a estos manuales

Sin comentarios