The PDRP-1002/PDRP-1002EAgent Release Control SystemManualSystem Sensor3825 Ohio AvenueSt. Charles, IL 601741-800-SENSOR2Fax: 630-377-6495PDRP1002.CDD
1 The PDRP-1002/PDRP-1002EAC Power10 The PDRP-1002 PN 51135:A 03/11/99SpecificationsAC PowerFor the PDRP-1002: 120 VAC, 50/60 Hz, 1.2 ampsFor the PD
RMS Regulated Power1 The PDRP-1002/PDRP-1002EThe PDRP-1002 PN 51135:A 03/11/99 11Figure 2 Cabinet DimensionsRPCABDIM.cdrDoor = 14.625 in.
2 System OperationRMS Regulated Power12 The PDRP-1002 PN 51135:A 03/11/992 System OperationWARNING:When used for CO2 releasing applications, observe
RMS Regulated Power2 System OperationThe PDRP-1002 PN 51135:A 03/11/99 13Control SwitchesTone SilenceAcknowledge alarms, troubles and supervisories.
2 System OperationRMS Regulated Power14 The PDRP-1002 PN 51135:A 03/11/99SupervisoryOutput circuit #4 is used as an input for monitoring supervisory
UL Power Limited Wiring Requirements3 Installation ProcedureThe PDRP-1002 PN 51135:A 03/11/99 153 Installation ProcedureGeneralCarefully unpack the
3 Installation ProcedureZones16 The PDRP-1002 PN 51135:A 03/11/99Initiating Device CircuitsZonesWire all alarm initiating devices sequentially for pr
Zones3 Installation ProcedureThe PDRP-1002 PN 51135:A 03/11/99 174-Wire Smoke Detector ConnectionsRefer to the Device Compatibility Document for suit
3 Installation ProcedureNotification Appliance Circuits18 The PDRP-1002 PN 51135:A 03/11/99Output CircuitsNotification Appliance CircuitsThis control
Alarm Relay3 Installation ProcedureThe PDRP-1002 PN 51135:A 03/11/99 19Alarm RelayOne Form-C dry alarm contact is provided in the basic panel for con
2 The PDRP-1002 PN 51135:A 03/11/99Installation Precautions – Adherence to the following will aid in problem-free installation with long-term reliabi
3 Installation ProcedureAC Power20 The PDRP-1002 PN 51135:A 03/11/99AC PowerPrimary power required for the PDRP-1002 panel is 120 VAC, 50/60 Hz, 1.2
Voltmeter/Ammeter3 Installation ProcedureThe PDRP-1002 PN 51135:A 03/11/99 21Optional ModulesThe fire control panel has two module connectors - J5 an
3 Installation ProcedureInstalling Option Modules22 The PDRP-1002 PN 51135:A 03/11/99Installing Option ModulesInsert the two stand-offs (provided) in
Transmitter Module - 4XTM (NOTIFIER)3 Installation ProcedureThe PDRP-1002 PN 51135:A 03/11/99 23Transmitter Module - 4XTM (NOTIFIER)Polarities shown
3 Installation ProcedureZone Relay Module - 4XZM (NOTIFIER)24 The PDRP-1002 PN 51135:A 03/11/99Zone Relay Module - 4XZM (NOTIFIER)Non-power limited a
LED Interface Module - 4XLM (NOTIFIER)3 Installation ProcedureThe PDRP-1002 PN 51135:A 03/11/99 25LED Interface Module - 4XLM (NOTIFIER)The wiring of
3 Installation ProcedureDIP Switch26 The PDRP-1002 PN 51135:A 03/11/99Setting Mode of OperationDIP SwitchThe DIP switch is located at the bottom of t
Output 4 Supervisory/Releasing Service3 Installation ProcedureThe PDRP-1002 PN 51135:A 03/11/99 27Output 4 Supervisory/Releasing ServiceSet the funct
Appendix A: Power CalculationsStandby Battery Requirements28 The PDRP-1002 PN 51135:A 03/11/99Appendix A: Power CalculationsStandby Battery Requireme
Ampere-Hour CalculationsAppendix A: Power CalculationsThe PDRP-1002 PN 51135:A 03/11/99 29Ampere-Hour CalculationsTable 2 Ampere-Hour CalculationsSe
The PDRP-1002 PN 51135:A 03/11/99 3
Appendix B: Device CompatibilityFM-Approved Releasing Devices30 The PDRP-1002 PN 51135:A 03/11/99Appendix B: Device Compatibility Table 3 UL Liste
FM-Approved Releasing DevicesAppendix B: Device CompatibilityThe PDRP-1002 PN 51135:A 03/11/99 318 in. orifice.Solenoid Group [C]Star Sprinkler Corp.
Appendix B: Device CompatibilityFM-Approved Releasing Devices32 The PDRP-1002 PN 51135:A 03/11/99 SYSTEM SENSORRated Vo l t a ge ²FWR DCFilteredDCSys
FM-Approved Releasing DevicesAppendix B: Device CompatibilityThe PDRP-1002 PN 51135:A 03/11/99 33System Sensor SP1R241575ADA Speaker/Signaling Strobe
Appendix B: Device CompatibilityFM-Approved Releasing Devices34 The PDRP-1002 PN 51135:A 03/11/99Table 6 UL Listed Notification AppliancesSystem Sen
FM-Approved Releasing DevicesAppendix B: Device CompatibilityThe PDRP-1002 PN 51135:A 03/11/99 35 Table 7 UL Listed, Compatible Two-Wire Smoke Detec
Appendix C: NFPA Standard-Specific RequirementsFM-Approved Releasing Devices36 The PDRP-1002 PN 51135:A 03/11/99Appendix C: NFPA Standard-Specific R
NFPA 72 Signaling Systems for Central Station ServiceAppendix C: NFPA Standard-Specific RequirementsThe PDRP-1002 PN 51135:A 03/11/99 37NFPA 72 Signa
Appendix C: NFPA Standard-Specific RequirementsNFPA 72 Signaling Systems for Central Station Service38 The PDRP-1002 PN 51135:A 03/11/99Using the MS-
NFPA 72 Auxiliary Fire Alarm SystemAppendix C: NFPA Standard-Specific RequirementsThe PDRP-1002 PN 51135:A 03/11/99 39NFPA 72 Auxiliary Fire Alarm Sy
4 The PDRP-1002 PN 51135:A 03/11/99
Appendix C: NFPA Standard-Specific RequirementsNFPA 72 Remote Station Fire Alarm System40 The PDRP-1002 PN 51135:A 03/11/99NFPA 72 Remote Station Fir
NFPA 72 Remote Station Fire Alarm SystemAppendix C: NFPA Standard-Specific RequirementsThe PDRP-1002 PN 51135:A 03/11/99 41Troubleshooting TableTable
Appendix C: NFPA Standard-Specific RequirementsNFPA 72 Remote Station Fire Alarm System42 The PDRP-1002 PN 51135:A 03/11/99Notes
NFPA 72 Remote Station Fire Alarm SystemAppendix C: NFPA Standard-Specific RequirementsThe PDRP-1002 PN 51135:A 03/11/99 43Notes
Appendix C: NFPA Standard-Specific RequirementsNFPA 72 Remote Station Fire Alarm System44 The PDRP-1002 PN 51135:A 03/11/99System Sensor3825 Ohio Ave
The PDRP-1002 PN 51135:A 03/11/99 5NFPA StandardsThis control panel complies with the following NFPA standards:NFPA 12 CO2 Extinguishing Systems (Hig
1 The PDRP-1002/PDRP-1002EInput Circuits6 The PDRP-1002 PN 51135:A 03/11/991 The PDRP-1002/PDRP-1002EFeatures• Microprocessor-controlled• Power-limi
Front Panel Control Switches1 The PDRP-1002/PDRP-1002EThe PDRP-1002 PN 51135:A 03/11/99 7Front Panel Control SwitchesSwitch 1 Tone SilenceSwitch 2 Al
1 The PDRP-1002/PDRP-1002ETransmitter Module (4XTM - NOTIFIER)8 The PDRP-1002 PN 51135:A 03/11/99Optional BoardsThe PDRP-1002/PDRP-1002E has mounting
Transmitter Module (4XTM - NOTIFIER)1 The PDRP-1002/PDRP-1002EThe PDRP-1002 PN 51135:A 03/11/99 9Transmitter Module (4XTM - NOTIFIER)For Local Energy