Setting Mode of Operation 2. Installation
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
29
Discharge Timer
Select the desired discharge timer setting by setting DIP Switches 3, 4 and 5 accordingly.
For NFPA 13 and 15 applications timer must be set to “Disabled”.
For NFPA 16 applications timer may be set to “10 Minutes” or “15 Minutes”.
Note: Timer will always start at Zone 2 normal to alarm transition. Upon timeout, corresponding release circuits will
shut off.
Note: Zone 1 will always override timer shutoff (except for Mode #4 - Split Release).
Disabled 10 Minutes 15 Minutes
Switch #3
OFF ON ON
Switch #4
OFF ON ON
Switch #5
OFF OFF ON