FAAST Fire Alarm Aspiration Sensing Technology® ModbusUSER GUIDE
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 110Holding Registers (Cont’d)Device StatusAddress Size (16-bit word
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 111Rev A0Sensor StatusThe device’s Sensor Status Structure is READ
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 112Sensor Status (Cont’d)Address Size (16-bit words)Parameter Name
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 113Rev A0Device LogsThe device’s Log Structure is READ ONLY and map
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 114Factory CongurationAddress Size (16-bit words)Parameter Name Ty
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 115Rev A0Device CongurationAddress Size (16-bit words)Parameter Na
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 116Device Conguration (Cont’d)Address Size (16-bit words)Parameter
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 117Rev A0Network CongurationAddress Size (16-bit words)Parameter N
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 118Appendix A. Congurable options on FAASTA.1. Alarm Conguration
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 119Rev A0A.2. Device Conguration VariablesName Description Range D
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 122Table of ContentsProduct Description ...
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 1Technical SupportSystem Sensor strives to provide our customers wi
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 13Rev A0Product DescriptionThe FAAST - Fire Alarm Aspiration Sensin
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 14Client InterfaceWhen a client is connected through Port 502, the
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 15Rev A0Device Sensor Status and Control OperationsDevice ReadThe M
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 16Device Sensor Status and Control Operations (Cont’d)Device TimeIn
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 17Rev A0Reading LogsIn order to read the device logs, the following
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 18Modbus CongurationThe device’s Modbus Configuration Structure is
User Guide: FAAST Fire Alarm Aspiration Sensing Technology® Modbus Protocol Schema 19Rev A0Holding RegistersNote: The Modbus Holding Register addresse