EPS40EXP and EPS120EXP Explosion Proof
Supervisory Pressure Switches
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Important
Please Read Carefully and Save
This instruction manual contains important information
about the installation and operation of supervisory pres-
sure switches. Purchasers who install switches for use by
others must leave this manual or a copy of it with the user.
Read all instructions carefully before installation, following
only those instructions that apply to the model you are
installing.
Before installing any alarm device, be thoroughly familiar
with:
NFPA 72: National Fire Alarm Code
NFPA 13: Installation of Sprinkler Systems
NFPA 25: Inspection, Testing, and Maintenance of Water-
based Fire Protection Systems
Other applicable NFPA standards, local codes, and the
requirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the
device to report an alarm condition. System Sensor is not
responsible for devices that have been improperly installed,
tested, or maintained.
Specifications
Contact Ratings: 10 A, 1/2 HP @ 125/250 VAC
2.5A @ 6/12/24 VDC
Operating Temperature Range: –40°F to +160°F
EPS40EXP EPS120EXP
Maximum Service Pressure (in PSI): 250 250
Adjustment Range: 10-100 10-200
Approximate Differential: 3 PSI @ 10 PSI 3 PSI @ 10 PSI
8 PSI @ 100 PSI 9 PSI @ 200 PSI
Enclosure Rating: NEMA Type 4 — Indoor/Outdoor use
Hazardous Atmospheres
Classification: Class I, Groups B, C, D, Div. 1
Class II, Groups E, F, G, Div. 1
Class III, Div. 1
Operation
As pressure changes, a diaphragm actuates 2 snap action
switches. The pressure switch actuation is determined by
adjustment settings.
Figure 1. Pressure switch basic dimensions:
Vista de pagina 0
1 2 3 4

Indice de contenidos

Pagina 1 - Supervisory Pressure Switches

COVER4.9"9.5"LOCKINGSCREWHEX ADJUSTSCREW1/4" HEX HEADCOVERTAMPERSET SCREW(WRENCHPROVIDED)ADJUSTMENTWHEELCOVER(WRENCHPROVIDED)MAIN ADJUS

Pagina 2 - D770-26-00 2 I56-1428-001R

BREAK WIRE AS SHOWN FORSUPERVISION OF CONNECTION.DO NOT ALLOW STRIPPED WIRELEADS TO EXTEND BEYONDSWITCH HOUSING. DO NOTLOOP WIRES.A78-2346-02D770-26-0

Pagina 3 - (Low Switch) (Hi Switch)

Adjustments To Factory SettingsTable 2.Dual-switch Model — EPS40EXP and EPS120EXP1. Install pressure switch as stated in “INSTALLATION”portion of inst

Pagina 4

D770-26-00 4 I56-1428-001R© System Sensor 2002Three-Year Limited WarrantySystem Sensor warrants its enclosed pressure switch to be free fromdefects in